standard conditions*
Capacity is rated under
the following standard conditions
|
Necessary Freezing
capacity calculation
for compressor selection
of WOCFIM Model buyer |
|
|
Water temperature 60F
(18C), incoming |
One
refrigeration ton (T)3.86kw(1.03TR) |
Refrigerant evaporator
temperature -15F (-26C), |
2. Required Ton (W) |
Condensing
temperature: 95F (35C) |
3. Heat exchange facor
(R) 1.15 |
thickness 7/8"(22mm)
28.5mm, 33.8mm
Crushed 3/16 -
1/4 thick can be produced by modificatioin of cutter |
4. Correction factor
according to supply water S |
Ambient temperature
40F -> 100F (5C ->38C), Data based 90F(33C) |
5. Evaporative temp
-25C base |
60Hz electrical
supply. Capacity will be less for higher
temperatures, 50 Hz |
CALCULATION
EXAMPLE |
Electric supply and on
units using expansion valves. |
Required
production ton :5 tons, Supply water temp 15C
Assiuming |
|
So the necessary
freezing capacity is asi follows: |
|
QKIW = T X W X R X S |
|
QKIW = T(i3.86) X
W(5TON) X R(1.15) X S(I.19)=26.I4KIW AT -25C ET |